To program a Hub, go to emx.packetpower.com and access the Open Power Interface (OPI) menu under the Manage tab.
Reference the following to complete common HUB functions. Click on a specific function for more detailed instructions.
Function | OPI Menu Item | Steps | Required field(s): Field definition |
Create a template | OPI Templates | Click (+) to create a template | Template name: Friendly template name Template SYSOID: Use "234234" for most Modbus applications Template protocol: Select Modbus or SNMP |
Add node template | OPI Templates | 1. Click on hyperlink of Template Nodes to expose Node / Reading templates 2. Complete all required fields 3. Click (+) to add node template | Node Template Name: Friendly node template name Node Type: Select template that closest resembles the device being monitored Voltage Rating: Nominal voltage for scaling Current Rating: Nominal current for scaling |
Add a specific device | OPI Devices | 1. Click (+) Add Device 2. Complete all required fields including "Enabled"
| Device IP: IP address of the device being monitored Device Name: Friendly name of the device being monitored Device Description: Friendly description of the device being monitored OPI Template: Template to be used HUB Device: GUID of the HUB being polled Enabled: Click to enable the HUB to start polling |
Assign registers to node template (for Modbus devices) | OPI Templates | 1. Click on hyperlink in "Template Nodes" column 2. Click on hyperlink in "Readings" column 3. Complete all required fields 4. Click (+) to add register to node map | Channel: Select the EMX channel that best resembles the matching register Scale: Scaling factor to apply to the reading Offset: Constant to add to scaled reading Register value = (Reading x Scale) + Offset Register: Device register number (may require adding the mfg's base address if that is not zero) Byte Mapping: Register byte type (typically F-ABCD) -- accounts for endianness and byte swapping |
Assign OID registers to node template (for SNMP devices) | OPI Templates | 1. Click on hyperlink in "Template Nodes" column 2. Click on hyperlink in "Readings" column 3. Complete all required fields 4. Click (+) to add register to node map | Channel: Select the EMX channel that best resembles the matching register Scale: Scaling or multiple Offset: Typically +1 or -1 or 0 OID: SNMP OID that corresponds to the MIB |
Configure device (Modbus settings) | OPI Devices | 1. Click on "Modbus" hyperlink in Device Credentials column 2. Complete all required fields | IP Port: Typically 502 for Modbus Unit ID: Modbus device ID (0-255) Protocol: Modbus |
Configure device (SNMP settings) | OPI Devices | 1. Click on "SNMP" hyperlink in Device Credentials column 2. Complete all required fields | SNMP Version: Select version 1, 2 or 3 Read Community: Typically "public" unless administrator has changed it Password: SNMP device access password |
Clone a device | OPI Devices | 1. Highlight device row and click "Clone" 2. Complete all required fields | New Device IP: IP address of the new device being monitored Device Name: Friendly name of the new device being monitored |
View device readings | OPI Readings | |
|
View GUID assigned to device | OPI Nodes |
|
|