Home / Power Monitoring / Current Transformers

Current Transformers


Packet Power products are calibrated for use with certain CTs. It is important that you use the meter with the CTs that it is calibrated for. Pay particular attention to CT orientation! The direction that the CT faces on the conductor matters. CTs installed backwards will produce negative power readings and may need to be reinstalled.

CT specification sheets, including important information on correct CT orientation, can be found here.

If you would like information on additional CT options, please contact support@packetpower.com..


Split Core AC CTs

Here are some of the most common split core CTs used with Packet Power's single-meter, multi-circuit and branch circuit monitors.


Nominal / Maximum Amperage (A)

Inside Diameter (mm)

External CT Dimensions

H x W x D (mm)

CT

Tail

(mm)

CT Output

Specification Sheet

15 / 18

10

39 x 23 x 26

100

mV

CT-XH10-xx-S-100MX

30 / 36

10

39 x 23 x 26

100

mV

CT-XH10-xx-S-100MX

50 / 63

10

39 x 23 x 26

100

mV

CT-XH10-xx-S-100MX

100 / 120

16

24

44 x 31 x 33

65 x 46 x 35

500

500

mV

mV

CT-XH16-100-S-500MX

CT-XH24-xxx-S

200 / 240

24

36

65 x 46 x 35

85 x 37 x 42

500

500

mV

mV

CT-XH24-xxx-S

CT-XH36-xxx-S

300 / 360

24

36

75 x 125

65 x 46 x 35

85 x 37 x 42

201 x 146 x 16

500

500

500

mV

mV

mV

CT-XH24-xxx-S

CT-XH36-xxx-S

CT-XH75X125-xxx-S

400 / 480

36

50 x 50

85 x 37 x 42

125 x 120 x 30

500

500

mV

mV

CT-XH36-xxx-S

CT-XH50X50-xxx-S

600 / 720

36

50 x 50

75 x 125

85 x 37 x 42

125 x 120 x 30

201 x 146 x 16

500

500

500

mV

mV

mV

CT-XH36-xxx-S

CT-XH50X50-xxx-S

CT-XH75X125-xxx-S

800 / 960

50 x 50

75 x 125

150 x 150

125 x 120 x 30

201 x 146 x 16

225 x 219 x 30

500

500

500

mV

mV

mV

CT-XH50X50-xxx-S

CT-XH75X125-xxx-S

CT-XH150-xxxx-S

1000 / 1200

75 x 125

150 x 150

201 x 146 x 16

225 x 219 x 30

500

500

mV

mV

CT-XH75X125-xxx-S

CT-XH150-xxxx-S

1200 / 1440

150 x 150

225 x 219 x 30

500

mV

CT-XH150-xxxx-S

1500 / 1800 75 x 125 201 x 146 x 16 500 mV CT-XH75X125-xxx-S

1600 / 1920

150 x 150

225 x 219 x 30

500

mV

CT-XH150-xxxx-S

2000 / 2400

150 x 150

225 x 219 x 30

500

mV

CT-XH150-xxxx-S

3000 / 3600

150 x 150

225 x 219 x 30

500

mV

CT-XH150-xxxx-S

4000 / 4800

150 x 150

225 x 219 x 30

500

mV

CT-XH150-xxxx-S



Solid Core AC CTs

Here are some of the most common solid core CTs used with Packet Power's single-meter and multi-circuit monitors.

 

Maximum Amperage (A)

Inside Diameter (mm)

External CT

Diameter x Depth (mm)

CT

Tail

(mm)

CT Output

Specification Sheet

35

9

22 x 9

200

mA or mV

CT-PP-35

60

15

30 x 9

200

mA or mV

CT-PP-60

200

32

69 x 29

2000

mV

CT-PP-200

400

32

69 x 29

2000

mV

CT-PP-400


Rogowski Coil Sensors

Packet Power offers flexible coil sensors in the following sizes for use with our single-meter and multi-circuit monitors.

 

Maximum Conductor Diameter

Coil Length

(mm)

Typical Amperage

Coil Lead

(mm)

68 mm / 2.66 in

250

100 to 1000A

3000

147 mm / 5.87 in

500

400 to 3000A

3000

211 mm / 8 in

700

1000 to 5000A

3000

306 mm / 12.6 in

1000

5000 to 10,000A

3000


Split Core DC CTs


Here are some of the most common split core Hall effect sensors for use with Packet Power's DC power monitors.


Maximum Amperage (A)

Inside Diameter (mm)

External CT Dimensions

H x W x D (mm)

CT

Tail

(mm)

Specification Sheet

30

16

46 x 29 x 30.8

1-3000

CT-DC-YH16-xxx-S

50

16

46 x 29 x 30.8

1-3000

CT-DC-YH16-xxx-S

100


16

21

35

42x13


46 x 29 x 30.8

61 x 60 x 16

91 x 85 x 22

49 x 92 x 32


1-3000
           CT-DC-YH16-xxx-S
CT-DC-YH35-xxx-S
CT-DC-YH21-xxx-S
CT-DC-YZ42X13-100-S

200

21

35

42x13

64x16

84x22


61 x 60 x 16
91 x 85 x 22
49 x 92 x 32
63 x 135 x 45
68 x 154 x 45

1-3000

CT-DC-YH21-xxx-S
CT-DC-YH35-xxx-S
CT-DC-YZ42x13-xxx-S
CT-DC-YH64X16-xxx-S
CT-DC-YH84x22-xxxx-S

300

21

35

65

42x13

84x22

61 x 60 x 16
91 x 85 x 22
127 x 147 x 26
49 x 92 x 32
68 x 154 x 45
1-3000
CT-DC-YH21-xxx-S
CT-DC-YH35-xxx-S
CT-DC-YH65-xxx-S
CT-DC-YZ42x13-xxx-S
CT-DC-YH84x22-xxxx-S

400

35

64x16

91 x 85 x 22
63 x 135 x 45
1-3000 CT-DC-YH35-xxx-S
CT-DC-YH64x16-xxx-S

500

35

91 x 85 x 22
1-3000 CT-DC-YH35-xxx-S
600 65 84x22 127 x 147 x 26
68 x 154 x 45
1-3000 CT-DC-YS65-xxx-S
CT-DC-YH84X22-xxxx-S

800

65

127 x 147 x 26 1-3000 CT-DC-YH65-800-S
1000 84x22 68 x 154 x 45 1-3000 CT-DC-YH84X22-xxxx-S
1200 65 127 x 147 x 26 1-3000 CT-DC-YH65-xxx-S

2000

100x42

86 x 175 x 46 various



Solid Core DC CTs

Here are some of the most common solid core Hall effect sensors for use with Packet Power's DC power monitors.


Maximum Amperage (A)

Inside Diameter (mm)

External CT Dimensions

H x W x D (mm)

CT

Tail

(mm)

Specification Sheet

300

40x30

65 x 90 x 38

various

CT-DC-YH40X30-xxx-B

400

40x30

65 x 90 x 38

various

CT-DC-YH40X30-xxx-B